Blanket 80: 80 kg/m³ rockwool blanket rated to 650°C

Vulcanite Armor Blanket 80: 80 kg/m³ basalt-dolomite rock wool stitched to galvanised or stainless steel wire mesh. Hot surface performance 650°C (ASTM C411/C447), thermal conductivity 0.038 W/mK at 50°C (ASTM C335), Flame Spread Index 0 (ASTM E84). Complies with ASTM C592 Type I and III.

  • ASTM C592 Type I and III compliant
  • Flame Spread Index 0 (ASTM E84)
Vulcanite Armor Blanket 80: 80 kg/m³ rock wool blanket rolls stitched to galvanised wire mesh

Buy online

Dispatch within 24 hours. Delivery within 72 hours. Collection from Vulcanite, Centurion.

50mm × 1200mm × 5m6 m²/roll · galvanised meshOn backorder
R1 412,55per roll Incl. VATR1 228,30 Excl. VAT · R235,43/m²
75mm × 1200mm × 3m3.6 m²/roll · galvanised meshOn backorder
R1 254,51per roll Incl. VATR1 090,88 Excl. VAT · R348,48/m²
100mm × 1200mm × 3m3.6 m²/roll · galvanised meshOn backorder
R1 658,66per roll Incl. VATR1 442,31 Excl. VAT · R460,74/m²

Special project pricing

50 rolls or more, or a thickness we do not list

Get a Quote

Vulcanite Armor Blanket 80: 80 kg/m³ basalt-dolomite rock wool stitched to galvanised or stainless steel wire mesh. Hot surface performance 650°C (ASTM C411/C447), thermal conductivity 0.038 W/mK at 50°C (ASTM C335), Flame Spread Index 0 (ASTM E84). Complies with ASTM C592 Type I and III.

  • Density 80 kg/m³ (EN1602)
  • Hot surface performance 650°C (ASTM C411 / ASTM C447)
  • Thermal conductivity 0.038 W/mK at 50°C, 0.058 W/mK at 200°C, 0.094 W/mK at 350°C (ASTM C335)
  • Linear shrinkage max 0.40% at maximum use temperature (ASTM C356), the lowest of the three grades
  • Flame Spread Index 0, Smoke Developed 20 (ASTM E84); water absorption <1 kg/m² partial immersion (EN1609 / BS 2972)

Technical parameters

Blanket 80 technical parameters from the Vulcanite Armor datasheet
Property Blanket 80 Standard
Density 80 kg/m³ EN1602
Hot surface performance 650 °C ASTM C411 / ASTM C447
k-value at 50°C mean 0.038 W/mK ASTM C335
k-value at 100°C mean 0.045 W/mK ASTM C335
k-value at 150°C mean 0.053 W/mK ASTM C335
k-value at 200°C mean 0.058 W/mK ASTM C335
k-value at 250°C mean 0.069 W/mK ASTM C335
k-value at 300°C mean 0.081 W/mK ASTM C335
k-value at 350°C mean 0.094 W/mK ASTM C335
Linear shrinkage max 0.4 % ASTM C356
Flame Spread Index 0 ASTM E84
Smoke Developed Index 20 ASTM E84
Water absorption, partial immersion < 1 kg/m² EN1609 / BS 2972
Standards EN1602, ASTM C335, ASTM C411, ASTM C447, ASTM C356, ASTM E84, EN1609, BS 2972, ASTM C592 Type I and III

Applications

  • Thermal and acoustic insulation of large-diameter piping, ducts and vessels where the hot-face temperature does not exceed 650°C
  • HVAC and process ducting
  • Air handling
  • Storage vessels and tanks
  • Lower-temperature process piping

Choose this grade if

The hot surface is at or below 650°C, or the application is ducting and vessels rather than high-temperature steam lines. Not the grade for surfaces above 650°C.

Compare the range

Blanket 80 questions

What is the maximum hot surface temperature for Blanket 80?

Blanket 80 is rated for hot surfaces up to 650°C, tested to ASTM C411 and ASTM C447.

How much does Blanket 80 shrink at its rated temperature?

Linear shrinkage for Blanket 80 is a maximum of 0.40% at its maximum use temperature, tested to ASTM C356.

When should I choose Blanket 80 over Blanket 100?

Choose Blanket 80 when the hot surface stays at or below 650°C and the application is ducting or vessels rather than high-temperature steam lines.

Full technical parameters on the datasheet

Every grade, every mean temperature and every test standard on one sheet.

Download Datasheet PDF, 536 KB